数据布线部件清单

In order to match other products in use on a particular public improvement either completed or in the course of completion.

Copper Cabling, 接线板s and Jacks

描述

Color

品牌

零件号

Category 6A Cabling – Plenum

黄色的

泛达/通用电缆公司 

7151852

24 Port 接线板 – Cat 6A

黑色的

泛达

DP246X88TGY

Mini-Com数据接口 – Cat 6A

黄色的

泛达

CJ6X88TGYL

迷你电话插孔 – Cat 6

白色

泛达

CJ688TGIW

Fiber Cabling, Enclosures and Connectors

描述

品牌

零件号

OM3 Multi-mode Fiber – 6 Strands, Armored

康宁

006 t8f - 31180 a1

OS2 Single-mode Fiber – 6 Strands, Armored

康宁

006年esf-t4101da1

OS2 Single-mode Fiber – 12 Strands, Armored

康宁

012年esf-t4101da1

MDF光纤框4U

康宁

CCH-04U

以色列国防军光纤框1U

康宁

CCH-01U

LC四轴MM面板

康宁

CCH-CP12-E4

LC Quad SM面板

康宁

CCH-CP24-A9

LC MM连接器

康宁

95-051-98-SP

LC - SM连接器

康宁

95-201-98-SP

LC MM连接器SOC

康宁

95-000-04

LC SM连接器SOC

康宁

95-000-04

数据线缆颜色

电缆类型

应用程序

Color

类别6A UTP


 


 


 


 

布线- 以色列国防军到墙壁

黄色的

布线—插接电缆

黄色的

接线板

黑色的

Mini-Com数据接口

黄色的

迷你电话插孔

白色/象牙

多模光纤- OM3


 

布线- MDF到以色列国防军

黑色的

布线—插接电缆

阿卡

单模光纤- OS2


 

布线- MDF到以色列国防军

黑色的

布线—插接电缆

黄色的

Standard Data Jack Quantities Per Room

标准教室

类型

数量. 

描述

墙上数据插孔

2

To be placed near Smart AV Classroom Lectern.

天花板数据插孔

2

To be placed in the center of the room above the dropped ceiling.

标准的办公室

类型

数量. 

描述

墙上数据插孔

2

To be placed near each employee’s computer workstation.

天花板数据插孔

2

To be placed in the center of the room above the dropped ceiling.

打印机数据插孔

2

For dedicated printer/copier locations.

Standard Fiber Optic Cabling

光纤主干

位置

描述

MDF

12 Strands of OS2 Single-mode to C Core
12 Strands of OS2 Single-mode to R Core
6 Strands of OM3 Multi-mode to Each 以色列国防军
6 Strands of OS2 Single-mode to Each 以色列国防军

以色列国防军

6 Strands of OM3 Multi-mode to MDF
6 Strands of OS2 Single-mode to MDF

电缆安装 

  1. All cables shall be pulled continuous without splice between patch panels and outlets.
  2. Cables shall be run in conduit down to the wall outlets. 塑料或金属表面 mounted raceways must be used where the raceway is shown exposed. 支撑钩必须 be used above accessible ceilings for cable without raceway. 所有电缆应正确 支持. Contractor must provide all materials including raceways.
  3. Cable shall be pulled and properly terminated by a California C-7 or C-10 licensed contractor with experience with telecommunication cabling.
  4. Conductors and cables shall be neatly fanned, laced, terminated and labeled at all 背板和橱柜.
  5. Device plates shall be of material and color as room decor.
  6. For each data jack installed, provide 1’ 黄色的 Cat 6A patch cords to connect from the patch panel to the switch.
  7. Document all network port according to the District’s network standard
    1. Provide a final as-built drawing of the TR and each jack number ex. 1.1-001

天花板数据插孔

  1. A 40’ service loop should be provided for all ceiling drops and should be neatly tie wrapped and coiled and properly 支持 by J-hooks.
  2. Ceiling drops shall be terminated into the appropriate Cat 6A Mini-Com jack placed within a surface mount biscuit with 2 ports. The surface mount biscuit shall be securely mounted above the dropped ceiling according to building code and 支持 by the 上部吊顶结构.
  3. If there is no dropped ceiling, then raceway and conduit should not be installed onto the surface of the exposed ceiling. If cabling is brought up to the ceiling from the floor then raceway shall be used and then a 2 port Mini-Com surface mount box shall be installed on the wall, one inch below the ceiling tile. 如果安装在一个位置 with very high ceilings, the surface mount box may be installed mid-wall if approved ITS管理.
  4. All cabling must be installed to comply with all building code and industry best practices including BICSI, ANSI/TIA and IEEE.

系统性能测试

  1. Provide all instruments for testing and demonstrating in the presence of the Owner's inspector that all circuits and wiring are free of shorts and grounds and that cabling has been properly installed without damage to the cable and properly terminated.
  2. Provide Cat 6A/fiber optic performance reports upon completion

For any questions regarding these specifications please contact the ITS服务台 通过访问 http://helpdesk.clqp888.com 或者发邮件给 helpdesk@帕萨迪纳市.edu.

认证 Standard - ACCJC Standard III. C.2

The institution continuously plans for, updates and replaces technology to ensure its technological infrastructure, quality and capacity are adequate to support its mission, operations, programs, and services.