数据布线标准
数据布线部件清单
In order to match other products in use on a particular public improvement either completed or in the course of completion.
Copper Cabling, 接线板s and Jacks
描述 |
Color |
品牌 |
零件号 |
---|---|---|---|
Category 6A Cabling – Plenum |
黄色的 |
泛达/通用电缆公司 |
7151852 |
24 Port 接线板 – Cat 6A |
黑色的 |
泛达 |
DP246X88TGY |
Mini-Com数据接口 – Cat 6A |
黄色的 |
泛达 |
CJ6X88TGYL |
迷你电话插孔 – Cat 6 |
白色 |
泛达 |
CJ688TGIW |
Fiber Cabling, Enclosures and Connectors
描述 |
品牌 |
零件号 |
---|---|---|
OM3 Multi-mode Fiber – 6 Strands, Armored |
康宁 |
006 t8f - 31180 a1 |
OS2 Single-mode Fiber – 6 Strands, Armored |
康宁 |
006年esf-t4101da1 |
OS2 Single-mode Fiber – 12 Strands, Armored |
康宁 |
012年esf-t4101da1 |
MDF光纤框4U |
康宁 |
CCH-04U |
以色列国防军光纤框1U |
康宁 |
CCH-01U |
LC四轴MM面板 |
康宁 |
CCH-CP12-E4 |
LC Quad SM面板 |
康宁 |
CCH-CP24-A9 |
LC MM连接器 |
康宁 |
95-051-98-SP |
LC - SM连接器 |
康宁 |
95-201-98-SP |
LC MM连接器SOC |
康宁 |
95-000-04 |
LC SM连接器SOC |
康宁 |
95-000-04 |
数据线缆颜色
电缆类型 |
应用程序 |
Color |
---|---|---|
类别6A UTP
|
布线- 以色列国防军到墙壁 |
黄色的 |
布线—插接电缆 |
黄色的 |
|
接线板 |
黑色的 |
|
Mini-Com数据接口 |
黄色的 |
|
迷你电话插孔 |
白色/象牙 |
|
多模光纤- OM3
|
布线- MDF到以色列国防军 |
黑色的 |
布线—插接电缆 |
阿卡 |
|
单模光纤- OS2
|
布线- MDF到以色列国防军 |
黑色的 |
布线—插接电缆 |
黄色的 |
Standard Data Jack Quantities Per Room
标准教室
类型 |
数量. |
描述 |
---|---|---|
墙上数据插孔 |
2 |
To be placed near Smart AV Classroom Lectern. |
天花板数据插孔 |
2 |
To be placed in the center of the room above the dropped ceiling. |
标准的办公室
类型 |
数量. |
描述 |
---|---|---|
墙上数据插孔 |
2 |
To be placed near each employee’s computer workstation. |
天花板数据插孔 |
2 |
To be placed in the center of the room above the dropped ceiling. |
打印机数据插孔 |
2 |
For dedicated printer/copier locations. |
Standard Fiber Optic Cabling
光纤主干
位置 |
描述 |
---|---|
MDF |
12 Strands of OS2 Single-mode to C Core |
以色列国防军 |
6 Strands of OM3 Multi-mode to MDF |
电缆安装
- All cables shall be pulled continuous without splice between patch panels and outlets.
- Cables shall be run in conduit down to the wall outlets. 塑料或金属表面 mounted raceways must be used where the raceway is shown exposed. 支撑钩必须 be used above accessible ceilings for cable without raceway. 所有电缆应正确 支持. Contractor must provide all materials including raceways.
- Cable shall be pulled and properly terminated by a California C-7 or C-10 licensed contractor with experience with telecommunication cabling.
- Conductors and cables shall be neatly fanned, laced, terminated and labeled at all 背板和橱柜.
- Device plates shall be of material and color as room decor.
- For each data jack installed, provide 1’ 黄色的 Cat 6A patch cords to connect from the patch panel to the switch.
- Document all network port according to the District’s network standard
- Provide a final as-built drawing of the TR and each jack number ex. 1.1-001
天花板数据插孔
- A 40’ service loop should be provided for all ceiling drops and should be neatly tie wrapped and coiled and properly 支持 by J-hooks.
- Ceiling drops shall be terminated into the appropriate Cat 6A Mini-Com jack placed within a surface mount biscuit with 2 ports. The surface mount biscuit shall be securely mounted above the dropped ceiling according to building code and 支持 by the 上部吊顶结构.
- If there is no dropped ceiling, then raceway and conduit should not be installed onto the surface of the exposed ceiling. If cabling is brought up to the ceiling from the floor then raceway shall be used and then a 2 port Mini-Com surface mount box shall be installed on the wall, one inch below the ceiling tile. 如果安装在一个位置 with very high ceilings, the surface mount box may be installed mid-wall if approved ITS管理.
- All cabling must be installed to comply with all building code and industry best practices including BICSI, ANSI/TIA and IEEE.
系统性能测试
- Provide all instruments for testing and demonstrating in the presence of the Owner's inspector that all circuits and wiring are free of shorts and grounds and that cabling has been properly installed without damage to the cable and properly terminated.
- Provide Cat 6A/fiber optic performance reports upon completion
For any questions regarding these specifications please contact the ITS服务台 通过访问 http://helpdesk.clqp888.com 或者发邮件给 helpdesk@帕萨迪纳市.edu.